Honeywell-Satronic Burner Control Box MMG 810.1/811.1
TYPES AVAILABLE
MMG 810.1
- Mod. 32 Art. Nr. 0640120
Mod. 33 Art. Nr. 0640220
Mod. 43 Art. Nr. 0642520
Mod. 45 Art. Nr. 0642620
MMG 811.1
- Mod. 33 Art. Nr. 0640520
Mod. 63 Art. Nr. 0640420
For 2-stage forced draught and combi oil/gas
burners
Suitable flame detectors:
– Ionisation probe
– UV sensor
– Infra-red flicker detector
INTRODUCTION
The MMG burner control box is capable of controlling
and monitoring forced draught and combi oil/gas burners
of any nominal rating (tested and approved as per EN 298).
The MMG 810.1 model 33 control boxes are also suitable for
use in stationary warm air generators (Direct air heaters
according to DIN 4794).
Different type and model designations identify the control
boxes according to varying national standards, and to some
extent, according to programme times.
TECHNICAL DATA
Supply voltage 220 / 240 V (-15… +10%)
50 Hz (50 – 60 Hz)
AC frequency variations result in proportional timing
deviations
Fuse rating max. 10 A rapid, 6 A slow
Power consumption 10 VA
Max. current per output
term. 3 2A, cos ϕ 0.2
term. 4, B 2A, cos ϕ 0.4
term. 5, 6, C 1A, cos ϕ 0.4
Total load 5A, cos ϕ 0.4
Amplifier sensitivity 1 µA
Min. current from UV tube
or ionisation probe 5 µA
Flame detector cable max. 20 m cable length
Air proving switch 1 terminal 4 A, 230 V
Reset delay none
Flame detector
– Ionisation probe
– Infra-red flicker detector IRD 1020.1 end-on
– UV tube type UVZ 780 red markings
installed radially or axially
Infra red flare detector IRD 1020
Weight incl. base 350 g
Mounting attitude any
Insulation standard IP 44
Permissable ambient temp. -20° C… +60° C
Classified acc. to EN 298 BTLLXN